Sta-Con Products logo
Quality Control Systems for Municipal & Industrial Installations
The Industry Benchmark Standard for a Quarter Century
Home Standards Services Products Catalog Employment Contact Us
Three Phase Monitor Operation
Three Phase Monitor When proper voltages are connected to the phase monitor, the internal relay energizes, the indicator lamp illuminates, and power application to the load is enabled. Any abnormal condition will cause the internal relay to de- energize, the indicator lamp will extinguish and power will be removed from the load until conditions return to normal. These units can be used on Delta or Wye systems, 50/ 60 HZ. Neutral wires are NOT required.
Specifications Customer Options
• Drop Out Voltage: +/- 10% of Operating   Voltage
• User Adjustable Voltage Set
• Output Rating: 10A @ 240VAC
• Hysteresis: 3% To Prevent Load Cycling
• Response Time: 
    Operate: < 1 Seconds
    Release: < 2 Seconds
• Power Dissipation: Less Than 2 Watts
• Operating Temp: -20° to +60°C
• Storage Temp: -45° to +85°C
• Enclosure: Lexan
• Base: Phenolic
• B = Time Delay on release & Operate (3- 5   seconds)
• G = Fixed Time Delay on Operate (5 seconds   to 1 hour)
• T = Adjustable Time Delay on Operate (5   seconds to 1 hour)
• U = Under Voltage Protection Only
• R = Manual Reset
Protects Against
• Phase Imbalance Over/ Under Voltage • Phase Loss/ Phase Shift Improper Phase Sequence
• Rapid Load Cycling Phase   Regeneration • Single Phasing

Control Panels can be manufactured to meet the following safety requirements:
• UL 913 for Hazardous Locations • UL 508
• Service Entrance Equipment • ETL

Back to Top  | Home  | Contact Us

Website design by MTB Software Solutions Inc.
Copyright © 2003 Sta-Con Incorporated